value range. The value is entered as minutes:seconds. If only one number is
entered, it will be interpreted as seconds.
High Alert Clear Point – If the alert is active and the parameter value falls below
the value in this field, the alert will become inactive.
Clear Delay – The parameter being monitored must fall below the High Alert
Clear Point value for longer than the time in this field in order for the alert to
become inactive. The value is entered as minutes:seconds. If only one number is
entered, it will be interpreted as seconds.
10.3.6.4.2 Low Alert
A low alert is used to signal you when a parameter value falls below a threshold
you determine. For example, you can set an alert to occur whenever the port
engine oil pressure rises falls below 40 PSI.
10.3.6.4.2.1 Parameters
A low alert and associated diagram are shown in the figure below.
Figure 88 – Low Alert Parameters
A low alert is triggered (i.e. becomes an active alert) once an input signal has
dropped below the Low Alert Set Point and the Set Delay time has elapsed. If the
Set Delay is set to zero, then the alert is immediately triggered once the input
signal drops below the Low Alert Set Point. The Set Delay is used to reduce false
or spurious alerts. As an example, setting the Set Delay to 5 seconds will
Revision 4.0.2 Page 258